XH-W3002 Digital Temperature Controller 10A Thermostat Control Switch with Probe Sensor Specifications:Product model: XH-W3002Temperature range: -50 ° C ~ 110 ° CTemperature control range: -50 ° C ~ 110 ° CTemperature measurement accuracy: ±0.2 °CTemperature control accuracy: ±0.1 °CInput power: DC12VOutput power: 120WOutput type: direct outputMounting hole distance: 73mm/2.87" (aperture 4mm/0.16")
Appearance size: 60 x 45 x 31mm/2.36 x 1.77 x 1.22"
Code setting table:
Code
|
Function
|
Setting range
|
Factory settings
|
P0
|
Starting temperature
|
-50℃~110℃
|
25
|
P1
|
Stop temperature
|
-50℃~110℃
|
40
|
P2
|
Temperature correction
|
-10℃~10℃
|
0℃
|
P3
|
Delayed start
|
0~10min
|
0min
|
Introduction to code and features:
P0 sets the startup temperaturePress the SET button to enter the internal menu. The default display is P0. Press the SET button again to set the desired start temperature with the up and down buttons.
P1 sets the stop temperaturePress the SET button to enter the internal menu. The display is P0. Press the up and down button to change to P1. Press the SET button again to set the desired stop temperature.
P2 set temperature correctionIn the same way, enter the internal menu, change to P2 by pressing the up and down buttons, press the setting button again, and set the required calibration temperature by the up and down buttons (detection temperature + correction temperature = actual temperature)
P3 set delay startIn the same way, enter the internal menu, change to P3 by pressing the up and down buttons, press the setting button again, and set the required delay time by the up and down buttons, the unit is minute. (Note: Delay start is generally used for compressor refrigeration. If English refrigerator freezer, this value needs to be set. According to compressor back pressure, it is generally set for 3-6 minutes. If it is not used to control compressor refrigeration, it does not need to be extended. Time function, skip directly.)Heating mode: starting temperature <stop temperature (program automatically determines heating mode)Cooling mode: starting temperature > stop temperature (program automatically determines cooling mode)
Common fault code
Code
|
Problem
|
Solution
|
888
|
Resetting
|
Waiting for normal display
|
LLL
|
Sensor open circuit
|
Repair or replace the sensor
|
HHH
|
Sensor short circuit
|